1、精品文档用电负荷及用电量计算表单 位序 号名称设备容量计算负荷备注Pe(kw)Pjs(kw)Qjs (KAR)Sjs (KVAIjs(A)甲乙 肝疫 苗车 间1工艺用电设备600450337.50Kx=0.752暖通用电设备16812694.50Kx=0.753给排水用电设备444433Kx=1.04照明设备3834.2025.65Kx=0.95小计850654.20490.656乘以同时利用系数588.78441.59735.981118.2 0Kp=Kq=0.9甲疫苗 车间7工艺用电设备600450337.50Kx=0.758暖通用电设备16812694.50Kx=0.759给排水用电设备
2、444433Kx=1.010照明设备3834.2025.65Kx=0.911小计850654.20490.6512乘以同时利用系数588.78441.59735.981118.2 0Kp=Kq=0.9水痘 疫苗 车间13工艺用电设备750525393.70Kx=0.7014暖通用电设备16812694.50Kx=0.7515给排水用电设备444433Kx=1.016照明设备3834.2025.65Kx=0.9017小计1000729.20546.9018乘以同时利用系数656.28492.21820.321246.4 0Kp=Kq=0.9其 它19综合办公室16011284140212.71K
3、x=0.7020动力站180135101.25168.75256.39Kx=0.7521动物房90725490136.7Kx=0.822锅炉房400320240400607.7Kx=0.823污水站3024183045.58Kx=0.824综合仓库2016122030.40Kx=0.825门卫及大门1812.609.4515.7523.93Kx=0.70全 厂26合计35982525.401894.127乘以同时利用系数2272.901704.7 0Kp=Kq=0.928采用电容补偿-96029补偿后合计2272.90744.702391.830变压器损耗2412031总计35982296.9
4、0864.702454.33728.9Y =81.8% (效率)Ws 总=3962153kwh/ 年表1-1本工程采用变电所集中补偿方式使功率因数保持在COSD: 0.9以上。冻干机、消防水泵、防排烟机、应急照明及其它消防用电设备属二级负荷,采用专线供电,并在末级设备用电自动投入装置保证供电,而厂区内其它用电设备均属三级负荷,对供电无特殊要求。Pe:设备容量,也就是设备标牌上所有额定功率之和,已知Kx:需求系数,COS):功率因数,这两个值是查表查的,见全国民用建筑工程设计技术措施表2.5.2-24欢通下载及 22.2.8Kp:Kq:Pjs Qjs SjsIjs Ijs同时系数(有功功率, (无功功率) (视在功率) (计算电流) (计算电流)计算负荷)=PeX Kx=Pjs x Kx=Pjs/COS ,=Pjs/1.73/0.38/COS (三项负荷),1.73=根号 3, 0.38=380/1000=Pjs/0.22/COS(单项负荷)欢迎您的下载,资料仅供参考!致力为企业和个人提供合同协议,策划案计划书,学习资料等等打造全网一站式需求