1、Uninterruptable Power SupplyUPS-(5-200)KVAUsers Manual使用手册11Brief introduction:UPS-(5-200KV) 3 phase in and 3phase out series UPS is large power and true online UPS with range from 5KVA to 200KVA, which adopts advanced digital design, high speed 16bit chip, ASIC, DDC and large power IGBT Handy wet t

2、owel go to wipe and get rid of the dirt.3.7. The battery must be changed by the professional and technical personnel, the battery changed out must deliver special circulation and give a new lease of life to the organization to deal with . The battery is “ poisonous waste material “ 3.8. UPS is not u

3、sed when being installed a long time, the battery disposed will discharge automatically, at the same time the automatic consumption that chemical energy of the battery, at 25 degrees Centigrade according to the environmental climate around, the battery must be charged in every three months, if the t

4、emperature is greater than 30 degrees Centigrade, the battery should be charged once every two months . Only need to start UPS while charging, and run at least for 24 hours under the normal work pattern. 4、working principle :4.1.UPS- 3/3 series UPS adopts advanced digital design, ,improved MTBF and

5、steadily,one lone main control panel control all system. Which adopts microprocessor control and ensure that machine can work steadily and reliably. Besides, UPS others parts: invert transformer, input inductance, IGBT, silicon controlled and switch.24.2.Standard UPS principle :4.3.Mains inverter pr

6、inciple:After AC input turn to DC filter through rectifier, then inverter invert through SPWM and output AC.4.3.1.Normal inverter model:Battery have been recharge full, after AC rectifier, then inverter output.34.3.2. Inverter normally, and battery recharge working model:battery voltage is low, afte

7、r AC inverter, on one hand it will charge, on the other inverter output. 4.3.3. AC input failure, battery-working model:AC input is failure, battery inverter and supply power. 4.3.4.Bypass output working model:There is AC input, but inverter has been closed, meantime, output is supplied bypass.4.4.

8、Function module 4.4.1.Rectifier 4 Protection short circuit rectifier switch Lightning arrestor 6/12 Plus rectifier Input inductance Battery temperature compensate Battery floating charging Battery timing balanced charging. The input of rectifier can be limited in rated numerical value, at the same t

9、ime , battery recharge in constant current, constant voltage, expert engineer can change rectifier working through setting parameter. 4.4.2.Inverter: Inverter output isolation transformer. 3 Phase PWM inverter bridge. Current sampling Voltage sampling Feedback control Selftesting Hardware sense Prot

10、ection circuit 55Front panel introduction: (1) LCD display-it indicates various kinds of data(2) LED statue display-it indicates working statue(3 Input rectifier switch -Control rectifier input(4) Bypass switch -Control bypass input.(5) Output switch -Control output(6) Battery switch -Control batter

11、y input(7) Maintenance bypass switch -Control AC bypass (just use it when maintenance)(8) Line bank-Connect input, output, battery and grounding.(9)RS232 communication port 6、INSTALLATION:6.1.Installation environment: Temperature:0+40 Relative humidity:30%90% Altitude:1000M Installation environment

12、dimension(LWH):200020002000 Board pressure:3000KG/M 2The indoor environment demanded is as following: No dust Appropriate indoor temperature: please operate UPS in 040,But it is 0when start, the idea operation temperature is 25. There should be a good heat dissipation system, the following is a feas

13、ible method:A: Natural ventilating system: Only suitable for low heat and vast space. B: man - made ventilating systems: Need to install the air conditioner when exceeds the peripheral temperature (TE) in chassis temperature (TA). As the TE and TA is close, the capacity of the heat distribution syst

14、em will increase. 2913 58674 ERSTNRSTN+-ERS23RS23RS2366.2. Check before installation:Unpack the equipment and inspect again to determine if any external or internal damage has occurred. Opening the main entrance, meantime, please check if all switches are disconnection.6.3.Installation site: Please

15、place the UPS in the place where keeps good ventilation, rear panel of UPS and two side faces should keep more than 80cm away from the wall. Do not lay goods on the UPS. It must have enough room to Overhaul in the front of equipment and above. Battery box of equipment must keep enough position on ri

16、ght-hand side for battery overhaul. Power line must be connected from bottom of machine.6.4.Terminal connection diagram:Before UPS is not being installed, please disconnect all switches.Left: R、S、T 、N connect three phase input phase line and median line ;Right :N 、R 、S、T connect three phase output p

17、hase line and median line;E connect earth line;+、- connect battery positive pole and negative pole.6.5.UPS three output system 5-200KVA cable specification: (unit: mm2)Input Output BatterycapacityR S T N E R S T N + -UPS-6KVA 6 6 6 6 6 6 6 6 6 8 8UPS-10KVA 6 6 6 6 6 6 6 6 6 10 10UPS-15KVA 10 10 10 1

18、0 10 10 10 10 10 20 20UPS-20KVA 10 10 10 10 10 10 10 10 10 20 20UPS-30KVA 16 16 16 16 16 16 16 16 16 30 30UPS-50KVA 25 25 25 25 25 25 25 25 25 50 50UPS-80KVA 40 40 40 40 40 40 40 40 40 80 80UPS-100KVA 50 50 50 50 50 50 50 50 50 100 100UPS-120KVA 60 60 60 60 60 60 60 60 60 120 120UPS-150KVA 75 75 75

19、75 75 75 75 75 75 150 150UPS-200KVA 100 100 100 100 100 100 100 100 100 200 2006.6Battery connection Opening battery pack. Installation battery on the corresponding position and connecting the good battery connecting wire6.7.connection inspectionconnect all input/output/battery/wire,check under matt

20、ers:R S T NInput N R S T Output +-Battery GroundingE E7 Whether all battery-connecting wires join correctly and keep in touch well, Input, output, the earth connection has already been connected in the corresponding wiring on the equipment is arranged correctly, The voltage of input end, frequency,

21、phase should keep the same with voltage of bypass, frequency, and phase.7、Specification:7.1 UPS series specification 7.1.1. Rectifier input parameter; Please refer to the following table 2Table 2Model 6KVA 10KVA 15KVA 20 KVA 30 KVA 40 KVA 50 KVA 60 KVA 80 KVA 100KVA 120 KVACapacity (KVA) 5 10 15 20

22、30 40 50 60 80 100 120Input single max. current 10 19 28 38 57 76 86 102 133 164 195Working way and principle On line,static bypass switch (zero transfer time ), Double switch technology, output power to totally isolatePhase 3phase +N+GNominal voltage 400VAC25%Nominal frequency 50Hz10%,60Hz10%Voltag

23、e harmonics distortion 10%Soft start 0100% 5sec7.1.2. Rectifier output parameter; Please refer to the following table 3Table 3Model 6KVA 10KVA 15KVA 20KVA 30KVA 40KVA 50KVA 60KVA 80KVA 100KVA 120KVAMax. output voltage 405VDCMicrocomputer setting charge current 3A30A(depend on battery capacity)7.2 Ba

24、ttery Please refer to the following table 4Table 4Model 6KVA 10KVA 15KVA 20KVA 30KVA 40KVA 50KVA 60KVA 80KVA 100KVA 120KVAMax.discharge current(A) 19 28 42 56 85 113 141 169 225 282 338Battery quantity 30pcsNominal battery voltage 360VDCFloating voltage 405VDCCharge current 3A30A(depend on battery c

25、apacity)7.3 Inverter specification Inverter Please refer to the following table 5Model 6KVA 10KVA 15KVA 20KVA 30KVA 40KVA 50KVA 60KVA 80KVA 100KVA 120KVARated power (KW)COS=0.8 7.2 12 18 24 36 40 60 72 97 121 145Phase 3phase +N+GNominal voltage 400VAC1%(steady load) ,400VAC5% (load fluctuate )Nomina

26、l frequency 50Hz0.05%,60Hz0.05%(battery supply power)Frequency stability:Out sync 0.05%Frequency stability:Synchronization 2%Crest factor 3:1Output wave Sine waveTotal harmonic distortion Linearity load 3%;non-linearity load5%8Dynamic load voltage transient (from 0 to 100% abrupt change)5%Moment res

27、tart time 10msBalance load voltage 1% ;5%(imbalance load voltage)Overload capability 125% 1min,150% 1SInverter efficiency,load 100% 91 91 91 92 92 93 93 93 95 95 957.4 Bypass Please refer to the following table 6Table 6Model 6KVA 10KVA 15KVA 20KVA 30KVA 40KVA 50KVA 60KVA 80KVA 100KVA 120KVAPhase 3ph

28、ase +N+GNominal voltage 400VAC25%Nominal frequency 50Hz5%,60Hz5%Inverter/bypass(transfer time) (overload)0ms7.5 systems specification:Please refer to the following table 6Table 6Model 6KVA 10KVA 15KVA 20KVA 30KVA 40KVA 50KVA 60KVA 80KVA 100KVA 120KVAEfficiency load 100% 80%PC communicationinterface

29、RS232Working temperature 040Humidity(noncondensing) 30%90%Working height(Max.) 1000m(per100m, power decline 1%,Max.4000m)Type of cooling Forced draughtNoise dB(according to load andtemperature)far away machine 1M 4050 5565Case color Gray (option )Input cable The bottom / backEasy maintenance The fro

30、nt / the above / left and right Dimension WDH(mm)7204501035600700135071072014507108501500 11008601680Weight(kg) 154 169 275 293 360 450 572 657 860 900 950Input device Terminal Output device Terminal *For reference only above data, GROUP reserves the right to implement changes to the above content w

31、ithout prior announcement. 8.Alarming:8.1 Alarming 1:Bypass voltage failure or bypass fuse SCR failure. It will alarm under these conditions:1. Bypass input voltage is wrong.2. Bypass input switch cut off.3. Bypass SCR fuse cut off or burned because of output short circuit or fuse cut off.8.2 Alarmi

32、ng 2:Main input power failure or rectifier input switch cut off. It will alarm under these conditions:1. Input voltage is not in the range(184287)V AC.2. Input frequency is not in the range(47.552.5)Hz.3. Rectifier input switch cut off.4. Because UPS is abnormal and cause one phase of three phase re

33、ctifier can not work normally, please find out the failure thought consult contents. 8.3Alarming 3:Battery low voltageIt will alarm under these conditions:1. Battery voltage is too low.92. The time battery running is shorter than setting time.8.4 Alarming 4:Battery discharge When battery discharge,

34、it will alarm at once, after 2 minutes, alarm will stop. Once battery discharge is up to battery final voltage, alarm again. 8.5 Alarming 5:Output overload. When load power is bigger than rated output voltage, namely, more than 100 %,if load current is over big, UPS will alarm. When UPS alarm, it ne

35、eds to reduce load capacity. Or UPS will turn to bypass, we get the time depend on over load values inverse ratio. 8.6 Alarming 6:Temporality bypass workingIt indicates bypass supply power; UPS will turn to normally run statue (inverter supply power). There are some conditions under this temporality

36、 statue, for example, overload, after bypass supply power, UPS is waiting for power supplied by inverter. 8.7 Alarming 7:Bypass output overloadIf overload time is too long, for example, overload 125%, inverter can supply power 1min. then turn to bypass. UPS will renew normal running statue. 8.8 Alar

37、ming 8:High temperature or fan failure When control system of UPS, inverter power module or rectifier power module is over temperature because of high temperature or fan failure, UPS turn to bypass.9UPS start up process:It must be operated to obey these sequence, thought there is battery switch in U

38、PS.Start up UPS:9.1.Open input rectifier switch(Up).9.2.Open bypass switch(UP )9.3.After battery low voltage indicator crust out, then open battery switch. (UP ) When UPS is no any alarm statue indicator, bypass will turn to inverter statue. 9.4.Open output switch(UP )Notice: it will display alarmin

39、g information about the wrong phase sequence if rectifier switch is not cut off, at this time, please press K1 and silence, carry out UPS start up process. 10UPS maintenance shut down process10.1.open maintenance switch(up)10.2.close battery switch(down)10.3.close rectifier switch(down)10.4.close by

40、pass switch(down)10.5.close UPS output switch(down)11. Emergency shut down process:When it happens to fire, electric shock, electric arc or other dangerous. user can read this process and operate, but it maybe cause the dangerous that no AC output. Make all switches cut off 1012Front panel introduct

41、ion:12.1 key introduction:K1: Functional grouping /silencing K2: start upK3: testing K4: settingK5: change screenK1+K2 shut down.12.2 Press key operation:system setting: Notice(plse do not change the original setting, or the wrong system setting will cause abnormal working ), after UPS work normally

42、, plse press K5 and look at all parameter and working statue, the display is as following:Display company informationUPS working statue information:Tble12-1UPS flow chartLEDDISPLAYFuse pedestaLEDDISPLAY11Tble12-2UPS input informationTble12-3UPS output information:Tble12-4UPS Battery and:Tble12-5UPS

43、Load Information:R Phase input voltage: 220VS Phase input voltage: 220VT Phase input voltage: 220VInput frequency: 50.0HzR Phase output voltage: 220VS Phase output voltage: 220VT Phase output voltage: 220VOutput frequency: 50.0HzBattery voltage:405V Charge current:00.0A Battery quantity:30PCS Batter

44、y capacity :000AHLoad Information:R phase current:000A S phase current:000A T phase current:000A 12Tble12-6UPS temperature :Tble12-7UPS parameter:Tble12-8If users can understand or want to get more detailed help to the content of the manual while using, please contact distributor or consult to our company, we will serve you heartily. Ambient Temp : 00R temperature: 00S temperature: 00T temperature: 00Bypass Working times: 000Battery Working times: 000Battery Working counter: 00:00HUPS capacity: CPTT-10KVA13