1、1智能建筑消防子系统的设计与实现【摘要】:随着我国智能建筑业的发展,高层建筑及建筑群体越来越多,从而也促进消防系统以迅猛的速度向前迈进,在智能建筑的设备自动化系统中消防系统是非常重要的一个子系统,本文主要介绍了消防系统中火灾自动报警系统和自动灭火控制系统。阐述了火灾自动报警系统(FAS)的主要原理和功能,并对建筑物中的主要报警设备和控制设备在系统中的作用进行了简单的说明。火灾自动报警系统和自动灭火控制系统之间的联动是本次设计的主要内容,自动灭火设备得到火灾报警信号后,按照事先编制的程序来完成灭火的全过程,所以编程是其中一项比较重要的任务。由于火灾自动报警及消防联动控制系统的自动化程度逐渐完善,
2、所以它在建筑防火中发挥着越来越大的作用,已成为一门新技术学科。【关键字】:智能建筑 消防监控 可编程控制器Abstract: With the development of intelligence building industry in our country,high buildings and building community are more and more,and that promote the fire fighting system to move forward with swift and violent speed.In intelligence construc
3、t of equipment automation,the fire fighting system is a very important subsystem.this text introduces the fire automatism alarming system and automatism extinguishing system in the fire fighting system,and expatiates the mostly elements and function of the fire automatism alarming system ,it simply
4、reports the function of mostly alarming equipment and cortrolling equipment in the building .the linkage between alarming system and extinguishing system is the mostly content of this design,when extinguishing equipment received the signal of fire alarm,it completes the entirely process of putting o
5、ut a fire according to prior formality,so programment is more important mission in the process.as a result of fire fighting systems automation gradually perfecting ,it very important in fireproofing and has been a new technic subject. keywords:Intelligent Building,fire fighting,PLC 1 概述1.1 智能建筑2现代化建
6、筑安装了越来越多的智能设备,我们称为智能建筑(Intellingent Building) 。智能建筑是采用先进的电子信息技术对建筑的设备进行自动监控,对信息资源进行有效管理和对用户提供信息服务的新型建筑。它通过对建筑物的四大要素(结构,系统,服务,管理)及其内在关联的最大优化考虑,为人们提供一个投资合理,高效,舒适,便利的环境,是高新技术与建筑艺术的有机结合。智能建筑中的智能化系统主要是由建筑设备自动化系统 BAS、通信网络系统 CNS 和办公自动化系统OAS 三大子系统组成。建筑设备自动化系统(Building Automation System)以计算机技术为核心,是一种将建筑物有关的设
7、备如电力、照明、空调通风、给排水、消防、保安、运输等设备集中监视、控制和管理的综合性的系统,以使设备安全、可靠的运行,节约能耗,节省人力。通信系统(Telecommunication System)包括以程控用户交换机为核心,以多功能电话、传真、各类终端为主要设备的通信网以及楼内局域网、工作站、高速主干通信网等,这些设备(包括软件)应用新的信息技术构成智能大厦信息的“中枢神经” 。办公自动化系统(Office Automation System)是办公业务借助于各种办公设备,并用这些设备与办公人员构成服务于,某种目标的人机信息系统。它主要作用是使信息收集和资料处理机械化和自动化,提高办公效率。
8、这里主要指利用计算机实现的办公自动化。该系统利用现代科学技术进行各种管理和交流各种信息,以提高管理水平,改善工作质量,加强决策能力。1.2 智能消防系统从消防的角度来看,消防系统应贯彻以防为主、防消结合的方针,及时发现并报告火情,控制火灾的发展,尽早扑灭火灾,确保人身安全和减少社会财富的损失,火灾的发生在其初期阶段往往只是规模甚小而有易于扑灭的,但是由于在火灾的初期阶段人们不易发觉或疏于防范,而使火灾蔓延,酿成灾难.长期以来,技术及管理人员都在追求一种易于管理,能对火灾的发生尽早报警而有准确的火灾自动报警控制系统,它对保障人们的生命安全具有非常重要的意义,它将使火灾的可能性降至最低点.为此,急
9、需提高对火灾的监测、报警和灭火控制技术以及消防系统的自动化水平。随着科技进步和生产发展,微电子技术、检测技术、自动控制技术和计算机技术等获得了迅猛的发展,并广泛消防技术领域,使火灾探测与自动报警技术、消防设备联动技术、消防通信调度指挥系统、火灾监控系统和消防控制中心等也取得了突飞猛进的发展,并逐步形成3了以火灾探测与自动报警为基本内容,计算机协调控制和管理各类消防灭火、防火设备,具有一定自动化和智能化水平的火灾监控系统,即智能消防系统。智能消防系统的设计内容应包括以下方面:总平面布局和平面布置中涉及消防安全的防火间距、消防车道、消防水源等;能够满足建筑火灾危险性类别和耐火等级要求的防火设计;建
10、筑防火防烟分区和建筑构防火造设计;安全疏散和消防电梯;防烟、排烟和通风、空调系统的防火设计;消防电源及其配电设计;火灾应急照明、应急广播和疏散指示标志;火灾自动报警控制系统极其联动等。其中火灾自动报警系统的设计又由为重要。本设计主要详细说明火灾自动报警系统极其联动。其基本原理如下图所示:1.3 可编程控制器从广义上来说,可编程控制器也是一种计算机控制系统,只不过它比一般的计算机具有更强的与工业过程相连接的接口和更直接的适用于控制要求的编程语言。所以PC 与计算机控制系统的组成十分相似,也具有中央处理器(CPU) 、存储器、输入/输出(I/O)接口、电源等。概括地讲,PC 的工作方式是一个不断循
11、环的顺序扫描过程。每一次扫描所用的时间称为扫描时间,也可以称为扫描周期或工作周期。顺序扫描工作方式简单直观,便于程序设计和 PC 自身的检查。具体体现在:PC 扫描到的功能经过解算后,其结果马上就可被后面将要扫描到的功能所利用,还可以在 PC 内设定一个监视定时器,用来监视每次扫描的时间是否超过规定值,避免由于内部 CPU 故障使程序执行进入死循环。扫描顺序可以是固定的,也可以是可变的。一般小型 PC 采用固定的扫描顺序,大中型 PC 采用可变的扫描顺序。这是因为大中型 PC 处理的 I/O 点数多,其中有些点可能不必要每次都扫描,一次扫描时对某一些 I/O 点进行,下次扫描时又对另一些I/O
12、 点进行,即分时分批地进行顺序扫描。这样做可以缩短扫描周期,提高实时控制火灾探测器手动火灾报警按钮火灾报警装置消防联动电源火灾报警控制器4中的响应速度。B取报警点总数loop i=1 to 32 doalarmSensori=0 ;清除残留报警点总数endlooploop i=1 to alarmTotal doalarmSensorSB.SB2PCC.Datai=1endloopendactionaction 2:开始变量初始化扫描探测器信号有火灾信号?Y 有故障信号?故障报警故障被清除手动报警B&R PCC紧急报警?预报警声光报警器动作所有消防器件动作扑灭火灾所有设备复位开始20myCod
13、e =SB.SB2PCC.CodeerrorTotal =SB.SB2PCC.Data0 ;取故障总数loop i=1 to 32 doerrorSensori=0 ;清除残留故障点数据endlooploop i=1 to errorTotal doerrorSensorSB.SB2PCC.Datai=1endloopendactionendcaseENDIF;预报警IF (alarmSensor1=1) OR (alarmSensor3=1) OR (SB1=1) OR (SB2=1) THENKA10=1ENDIFIF (alarmSensor2=1) OR (alarmSensor4=1
14、) OR (alarmSensor5=1) OR (alarmSensor6=1) OR (SB3=1) OR (SB4=1) OR (SB5=1) THEN ;火灾报警极其相关联动动作KA1=1KA2=1KA3=1KA4=1 KA5=1KA6=1ZA1=1KA8=1KA9=1KA10=1KA11=1KA12=1KA13=1KA14=1KA15=1ENDIFIF ZA1=1 THEN ;卷帘门动作过程a=a+1ENDIFIF (a0) AND (a500) AND (a1000)AND(a1500 THEN21KA7=0ZA1=0a=0ENDIFselect stepReset ;火灾自动报警
15、控制与 PCC 间进行信号传输,实现相应器件的动作state DIANYUANwhen(latch_XSB6=1)latch_XSB6=0ZA1=0loop i=0 to 32 doalarmSensori=0SB.SB2PCC.Datai=0endloopmyCode=0alarmTotal=0KA1=0KA2=0KA3=0KA4=0KA5=0KA6=0KA7=0KA8=0KA9=0KA10=0KA11=0KA12=0KA13=0KA14=0KA15=0next WAIT when(SB.statusMSG_SERVICE_ACTIF SB.status=0 THEN acOrDc =SB.
16、PCC2SB.Data0acErr =SB.PCC2SB.Data1dcErr =SB.PCC2SB.Data2ENDIFnext IDLE_WAITstate IDLE_WAITinc(uu)when uu10022uu=0NEXT DIANYUANstate WAITinc(uu)when uu100uu=0next CLEAR_SNDstate CLEAR_SNDSB.PCC2SB.CmdCode =102SB.PCC2SB.service =1when 1=1next RESET_SBstate RESET_SBwhen SB.statusMSG_SERVICE_ACTSB.PCC2S
17、B.CmdCode =101SB.PCC2SB.service =1next DIANYUANendselectIF SB7=1 THEN ;手动控制模拟控制相应器件动作KA6=1ENDIFIF SB8=1 THENKA8=1ENDIFIF SB9=1 THENKA2=1ENDIFIF (KA2=1) AND (SKA=1) THEN ;消防泵反馈信号KA5=1ELSEKA5=0ENDIFIF SB10=1 THENKA9=1 ENDIFIF SB11=1 THENKA8=1ENDIFIF SB12=1 THENKA3=1ENDIFIF (KA3=1) AND (KKA=1) THEN ;空调
18、反馈信号KA12=1ELSEKA12=0ENDIF23IF SB13=1 THENKA4=1ENDIFIF (TKA=1) AND KA4=1) THEN ; 电梯反馈信号KA11=1 ELSEKA11=0ENDIFIF SB14=1 THENKA1=1ENDIF IF (GKA=1) AND (KA1=1) THEN ; 供配电反馈信号KA13=1ELSEKA13=0ENDIFIF SB15=1 THENKA15=1ENDIFIF SB16=1 THENKA16=1ENDIFIF SB6=1 THENKA1=0KA2=0KA3=0KA4=0KA5=0KA6=0KA7=0KA8=0KA9=0K
19、A10=0KA11=0KA12=0KA13=0KA14=0KA15=0ZA1=0a=0ENDIF附录 3 程序变量列表24Name Scope Data TypeLength I/O-Type 备 注SB pcc_global typSB 1 INTERNALacErr local BYTE 1 INTERNALacOrDc local BYTE 1 INTERNALalarmSensor local BIT 33 INTERNALalarmTotal local BYTE 1 INTERNALdcErr local BYTE 1 INTERNALerrorSensor local BIT 3
20、3 INTERNALerrorTotal local BYTE 1 INTERNALi local BYTE 1 INTERNALa tc_global INT32 1 INTERNALZA1 tc_global INT32 1 INTERNALka1 tc_global BIT 1 QP3.1.1 声光报警器ka10 tc_global BIT 1 QP3.2.2 声光报警器指示灯ka11 tc_global BIT 1 QP3.2.4 电梯迫降指示灯ka12 tc_global BIT 1 QP3.2.5 空调停止指示灯ka13 tc_global BIT 1 QP3.2.6 电源切换指示
21、灯ka14 tc_global BIT 1 QP3.2.7 消防广播指示灯ka15 tc_global BIT 1 QP3.2.8 应急灯指示灯ka2 tc_global BIT 1 QP3.1.2 启动消防泵信号ka3 tc_global BIT 1 QP3.1.3 空调停止信号ka4 tc_global BIT 1 QP3.1.4 电梯迫降信号ka5 tc_global BIT 1 QP3.1.5 消防泵指示灯ka6 tc_global BIT 1 QP3.1.6 喷淋泵运行信号极其指示灯ka7 tc_global BIT 1 QP3.1.7 卷帘门动作及指示灯ka8 tc_global
22、BIT 1 QP3.1.8 防火阀信号及指示灯ka9 tc_global BIT 1 QP3.2.1 排烟阀信号及指示灯25latch_sb6 local BIT 1 INTERNALmyCode local BYTE 1 INTERNALsb1 tc_global BIT 1 IP3.1.1 模拟离子感烟按钮sb2 tc_global BIT 1 IP3.1.2 模拟光电感烟按钮sb3 tc_global BIT 1 IP3.1.3 模拟温感按钮sb4 tc_global BIT 1 IP3.1.4 模拟手报按钮sb5 tc_global BIT 1 IP3.1.5 模拟消火栓按钮sb6 t
23、c_global BIT 1 IP3.1.6 停止按钮sb7 tc_global BIT 1 IP3.1.7 喷淋泵(手动)sb8 tc_global BIT 1 IP3.1.8 卷帘门(手动)sb9 tc_global BIT 1 IP3.2.1 消防泵(手动)sb10 tc_global BIT 1 IP3.2.2 排烟阀(手动)sb11 tc_global BIT 1 IP3.2.3 防火阀(手动)sb12 tc_global BIT 1 IP3.2.4 空调停止按钮sb13 tc_global BIT 1 IP3.2.5 电梯迫降按钮sb14 tc_global BIT 1 IP3.2
24、.6 电源切换按钮sb15 tc_global BIT 1 IP3.2.7 消防广播按钮sb16 tc_global BIT 1 IP3.2.8 应急灯按钮GKA tc_global BIT 1 IP3.3.1 电源切换反馈信号SKA tc_global BIT 1 IP3.3.2 消防泵反馈信号KKA tc_global BIT 1 IP3.3.3. 空调停止反馈信号TKA tc_global BIT 1 IP3.3.4 电梯迫降反馈信号stepReset local WORD 1 INTERNALuu local WORD 1 INTERNALalarmSensor1 local BIT 1 INTERNAL 光电感烟alarmSensor2 local BIT 1 INTERNAL 温感alarmSensor3 local BIT 1 INTERNAL 离子感烟alarmSensor4 local BIT 1 INTERNAL 手报按钮alarmSensor5 local BIT 1 INTERNAL 消火栓按钮alarmSensor6 local BIT 1 INTERNAL 定温电缆