资源描述

1、Signallist B&R Control Cabinets HCS & PCS HP BypassNo. ID-No. Description From/To Range Unit Signaltype IO-Type for DCS Contact FunctionHCS 0LBF10GH1001 0LBF10GH100XJ91 Ready for Service HCS/DCS - - pot.free contact DI NO Signal for DCS2 0LBF10GH100XJ92 Warning HCS/DCS - - pot.free contact DI NO Sig

2、nal for DCS3 0LBF10GH100XJ93 Alarm HCS/DCS - - pot.free contact DI NO Signal for DCSPCS1 HP11+13 Bypass 0LBF10GH1111 0LBF11AA101XQ01 Setpoint HP Bypass Control Valve DCS/PCS 0-100 % 4-20mA AO - Setpoint position value2 0LBF11CG101XQ01 Actual Position HP Bypass Control Valve PCS/DCS 0-100 % 4-20mA AI

3、 - Actual position value3 0LBF11AA101XB11 Quick open HP Bypass Control Valve DCS/PCS - - 24VDC DO NO Command to valve4 0LBF11AA101XB01 Limitswitch open HP Bypass Control Valve PCS/DCS - - pot.free contact DI NO Signal for DCS5 0LBF11AA101XB02 Limitswitch close HP Bypass Control Valve PCS/DCS - - pot

4、.free contact DI NO Signal for DCS6 0LBF50AA111XQ01 Setpoint HP Water Control Valve DCS/PCS 0-100 % 4-20mA AO - Setpoint position value7 0LBF50CG111XQ01 Actual Position HP Water Control Valve PCS/DCS 0-100 % 4-20mA AI - Actual position value8 0LBF50AA111XB11 Quick open HP Water Control Valve DCS/PCS

5、 - - 24VDC DO NO Command to valve10 0LBF50AA111XB01 Limitswitch open HP Water Control Valve PCS/DCS - - pot.free contact DI NO Signal for DCS11 0LBF50AA111XB02 Limitswitch close HP Water Control Valve PCS/DCS - - pot.free contact DI NO Signal for DCS12 0LBF50AA011XB11 Open/Close HP Water Stopvalve D

6、CS/PCS - - 24VDC DO NO Command to valve13 0LBF50AA011XB01 Limitswitch open HP Water Stopvalve PCS/DCS - - pot.free contact DI NO Signal for DCS14 0LBF50AA011XB02 Limitswitch close HP Water Stopvalve PCS/DCS - - pot.free contact DI NO Signal for DCS15 0LBF10GH111XJ91 Controller failure PCS/DCS - - po

7、t.free contact DI NC Signal for DCS16 0LBF10GH111XJ92 Fuse tripped PCS/DCS - - pot.free contact DI NC Signal for DCS17 0LBF10GH111XJ93 MT5356 in Testmode PCS/DCS - - pot.free contact DI NC Signal for DCS18 0LBF10GH111XJ94 MT5356 Pressureswitch tripped PCS/DCS - - pot.free contact DI NC Signal for DC

8、S19 PB Control desk open all Bypass valves contact 1Control desk/PCS - - pot.free contact - NC Signal from Control desk1 0LBF13AA101XQ01 Setpoint HP Bypass Control Valve DCS/PCS 0-100 % 4-20mA AO - Setpoint position value2 0LBF13CG101XQ01 Actual Position HP Bypass Control Valve PCS/DCS 0-100 % 4-20m

9、A AI - Actual position value3 0LBF13AA101XB11 Quick open HP Bypass Control Valve DCS/PCS - - 24VDC DO NO Command to valve4 0LBF13AA101XB01 Limitswitch open HP Bypass Control Valve PCS/DCS - - pot.free contact DI NO Signal for DCS5 0LBF13AA101XB02 Limitswitch close HP Bypass Control Valve PCS/DCS - -

10、 pot.free contact DI NO Signal for DCS6 0LBF50AA113XQ01 Setpoint HP Water Control Valve DCS/PCS 0-100 % 4-20mA AO - Setpoint position value7 0LBF50CG113XQ01 Actual Position HP Water Control Valve PCS/DCS 0-100 % 4-20mA AI - Actual position value8 0LBF50AA113XB11 Quick open HP Water Control Valve DCS

11、/PCS - - 24VDC DO NO Command to valve10 0LBF50AA113XB01 Limitswitch open HP Water Control Valve PCS/DCS - - pot.free contact DI NO Signal for DCS11 0LBF50AA113XB02 Limitswitch close HP Water Control Valve PCS/DCS - - pot.free contact DI NO Signal for DCS12 0LBF50AA013XB11 Open/Close HP Water Stopval

12、ve DCS/PCS - - 24VDC DO NO Command to valve13 0LBF50AA013XB01 Limitswitch open HP Water Stopvalve PCS/DCS - - pot.free contact DI NO Signal for DCS14 0LBF50AA013XB02 Limitswitch close HP Water Stopvalve PCS/DCS - - pot.free contact DI NO Signal for DCS15 0LBF13GH111XJ91 Controller failure PCS/DCS -

13、- pot.free contact DI NC Signal for DCS16 0LBF13GH111XJ92 Fuse tripped PCS/DCS - - pot.free contact DI NC Signal for DCS17 PB Control desk open all Bypass valves contact 2Control desk/PCS - - pot.free contact - NC Signal from Control deskPCS2 HP12+14 Bypass 0LBF10GH1121 0LBF12AA101XQ01 Setpoint HP B

14、ypass Control Valve DCS/PCS 0-100 % 4-20mA AO - Setpoint position value2 0LBF12CG101XQ01 Actual Position HP Bypass Control Valve PCS/DCS 0-100 % 4-20mA AI - Actual position value3 0LBF12AA101XB11 Quick open HP Bypass Control Valve DCS/PCS - - 24VDC DO NO Command to valve4 0LBF12AA101XB01 Limitswitch

15、 open HP Bypass Control Valve PCS/DCS - - pot.free contact DI NO Signal for DCS5 0LBF12AA101XB02 Limitswitch close HP Bypass Control Valve PCS/DCS - - pot.free contact DI NO Signal for DCS6 0LBF50AA112XQ01 Setpoint HP Water Control Valve DCS/PCS 0-100 % 4-20mA AO - Setpoint position value7 0LBF50CG1

16、12XQ01 Actual Position HP Water Control Valve PCS/DCS 0-100 % 4-20mA AI - Actual position value8 0LBF50AA112XB11 Quick open HP Water Control Valve DCS/PCS - - 24VDC DO NO Command to valve10 0LBF50AA112XB01 Limitswitch open HP Water Control Valve PCS/DCS - - pot.free contact DI NO Signal for DCS11 0L

17、BF50AA112XB02 Limitswitch close HP Water Control Valve PCS/DCS - - pot.free contact DI NO Signal for DCS12 0LBF50AA012XB11 Open/Close HP Water Stopvalve DCS/PCS - - 24VDC DO NO Command to valve12 0LBF50AA012XB01 Limitswitch open HP Water Stopvalve PCS/DCS - - pot.free contact DI NO Signal for DCS14

18、0LBF50AA012XB02 Limitswitch close HP Water Stopvalve PCS/DCS - - pot.free contact DI NO Signal for DCS15 0LBF10GH112XJ91 Controller failure PCS/DCS - - pot.free contact DI NC Signal for DCS16 0LBF10GH112XJ92 Fuse tripped PCS/DCS - - pot.free contact DI NC Signal for DCS17 PB Control desk open all By

19、pass valves contact 3Control desk/PCS - - pot.free contact - NC Signal from Control desk1 0LBF14AA101XQ01 Setpoint HP Bypass Control Valve DCS/PCS 0-100 % 4-20mA AO - Setpoint position value2 0LBF14CG101XQ01 Actual Position HP Bypass Control Valve PCS/DCS 0-100 % 4-20mA AI - Actual position value3 0

20、LBF14AA101XB11 Quick open HP Bypass Control Valve DCS/PCS - - 24VDC DO NO Command to valve4 0LBF14AA101XB01 Limitswitch open HP Bypass Control Valve PCS/DCS - - pot.free contact DI NO Signal for DCS5 0LBF14AA101XB02 Limitswitch close HP Bypass Control Valve PCS/DCS - - pot.free contact DI NO Signal

21、for DCS6 0LBF50AA114XQ01 Setpoint HP Water Control Valve DCS/PCS 0-100 % 4-20mA AO - Setpoint position value7 0LBF50CG114XQ01 Actual Position HP Water Control Valve PCS/DCS 0-100 % 4-20mA AI - Actual position value8 0LBF50AA114XB11 Quick open HP Water Control Valve DCS/PCS - - 24VDC DO NO Command to

22、 valve10 0LBF50AA114XB01 Limitswitch open HP Water Control Valve PCS/DCS - - pot.free contact DI NO Signal for DCS11 0LBF50AA114XB02 Limitswitch close HP Water Control Valve PCS/DCS - - pot.free contact DI NO Signal for DCS12 0LBF50AA014XB11 Open/Close HP Water Stopvalve DCS/PCS - - 24VDC DO NO Comm

23、and to valve14 0LBF50AA014XB01 Limitswitch open HP Water Stopvalve PCS/DCS - - pot.free contact DI NO Signal for DCS14 0LBF50AA014XB02 Limitswitch close HP Water Stopvalve PCS/DCS - - pot.free contact DI NO Signal for DCS15 0LBF10GH114XJ91 Controller failure PCS/DCS - - pot.free contact DI NC Signal

24、 for DCS16 0LBF10GH114XJ92 Fuse tripped PCS/DCS - - pot.free contact DI NC Signal for DCS17 PB Control desk open all Bypass valves contact 4Control desk/PCS - - pot.free contact - NC Signal from Control deskMeasuring a Testing Unit HP 0LBF10GH101 2006/8/21Measuring a Testing Unit HP 0LBF10GH102Junction Box HP Byp 0LBF11GH101