收藏 分享(赏)

2005矿用防爆产品选用手册华荣.pdf

上传人:精品资料 文档编号:11050278 上传时间:2020-02-05 格式:PDF 页数:74 大小:1.88MB
下载 相关 举报
2005矿用防爆产品选用手册华荣.pdf_第1页
第1页 / 共74页
2005矿用防爆产品选用手册华荣.pdf_第2页
第2页 / 共74页
2005矿用防爆产品选用手册华荣.pdf_第3页
第3页 / 共74页
2005矿用防爆产品选用手册华荣.pdf_第4页
第4页 / 共74页
2005矿用防爆产品选用手册华荣.pdf_第5页
第5页 / 共74页
点击查看更多>>
资源描述

1、BGP- 10(6) WAROM 01 Series mining flame-proof intelligentized high voltage vacuum distribu- tion system Model Instruction Rated voltage(V) Rated current(A) Vacuum distribution system High voltage Explosion-proof type B G P- 10 / (6) Main technical parameters 1176 42 78 Outline measure Cables outer d

2、ia. (,mm) Application The distribution system is mainly used under coal mine which is full of explosive dangerous gas such as methane mixture, control the dis- tribution system of rated voltage 6KV or 10KV frequency of 50Hz, rated current from 50A to 630As three-phrase AC-neutral point which connect

3、s earth undirectly, protect and measure and can start directly for high-voltage motor. 1. The breaker is hand cart type,which can be drawn out outside ofenclose without additional rail, with strong interchange ability,convenient for installation and maintenance. 2. Isolated switch is club contactor,

4、 with long life low contactresistance. 3. High pressure integrated protect device is intelligent type, withstriking LCD screen.with only three adjustable operate button,can complete overload, short-circuit,creepage isolating monitor,all the tests and checks, can display all the parameter values inop

5、eration by shift button and all the operation datas and failurecauses in Chinese as well, can realize online communication,central control, remote control,wind and electric locked, failurecauses time self-recorded. 4. Direct reading, measured by three phases and three wined instrument. 5. All the in

6、struments are displayed by number. intuitionistic clearand striking. 6. Main circuits are all connected by hard busbars instead of softones with the failure rate zero. 7. Can connect with various types (a.Left entry b.right entry c.double power supply d.contra entry e.connection), use only onebusbar

7、 room to reduce facility setting area. Product features Rated short-circuit sustained time(S) Rated short-circuit open-breaking current(KA) Machinery life(PCS) Rated voltage(V) Product type Rated current(A) Rated peak value tolerated current(KA) BGP-630/6 6 50,100,150,200,250,315,400,630 12.5 31.5 4

8、 10000 BGP-630/10 10 50,100,150,200,250,315,400,630 12.5 31.5 4 10000WAROM 02 Series mining flame-proof high voltage vacuum distribution system Application The distribution system is mainly used under coal mine which is full of explosive dangerous gas such as methane mixture, control protect and mea

9、sure the distribution system with rated voltage 6KV or 10KV, rated current from 50A to 630As three-phase AC-neutral point which connects earth indirectly, and can start directly for high voltage motor. Product features 1. Digital microcomputer procedure controlling device. 2. Have protections of lea

10、kage, voltage-absent, under voltage andoverload voltage. 3. Small volume, light weight and be convenient to install and maintain. Model Instruction B G P 43 10 / (6) Main technical parameters 2 Seconds thermal stability current Machinery life(PCS) Operating over-voltage multiple 1284 42 78 Product t

11、ype Rated voltage(V) Rated current(A) Open-breaking capacity(MV A) Open-breaking current(KA) Outline measure (mm) Cables outer dia. (,mm) BGP43-10 10 50,100,150,200,315,400,630 200 12.5 12.5 10000 3 Under 3 times relative voltage peak-value BGP43-6 6 50,100,150,200,250,315,400,630 100 12.5 12.5 1000

12、0 3 Under 3 times relative voltage peak-value BGP43- 10(6) Rated voltage(V) Rated current(A) Design No. Vacuum distribution system High voltage Explosion-proof typeQBGZ- 10(6) WAROM 03 Model Instruction Q B G Z- 630 / (6)10 Main technical parameters Product type Rated voltage(V) Rated current(A) Mac

13、hinery life(PCS) 42 78 Outline measure(mm) Cables outer dia. (,mm) Series mining flame-proof intelligentized high voltage vacuum electromagnetic resistant starter The starter is mainly used under coal mine full of explosive danger- ous gas such as methane mixture, start, stop and control the high vo

14、ltage motor, and protect electrical motor and related circuits at the same time, with the rated voltage 6KV, 10KV, frequency 50Hz, rated current 50A to 400A at circuit. Application Product features 1. The high voltage vacuum circuit electrimaguet starter adopts squarecase, quick door. 2. The hi-qres

15、sure vacuum contactor is hand cart tyqe. Can be drawnout of enclosure without additional rail,with strong interchangeability, easy to install and maintain. 3. Match with advanced intelligentized protection performances ofcreepage, monitor anti-time limit, over-current, short-circuit, phase-off, lack

16、 of voltage, voltage-absent, over-voltage. QBGZ-630/6 6 50,100,150,200,300,400,630 4( )Effective value 4( )Peak value 2 100000( ) QBGZ-630/10 10 50,100,150,200,300,400,630 4( )Effective value 4( )Peak value 2 100000( ) Open-breaking current(KA) Rated short-circuit sustained time(S) Rated peak value

17、tolerated current(KA) Rated voltage(V) Rated current(A) Vacuum High voltage Explosion-proof type StarterWAROM 04 KBZ-500 630(Y) Mining flame-proof vacuum electricity-presenting switch The series feeding switches are used under coal mine which is full of explosive mixture gas such as methane, coal-du

18、st and so on in me- dium surrounded, in circuits of AC 50Hz, rated voltage 1140V , rated current to 630A, it can be as moving substation using electricity-pre- senting switch (connect coverboard with moving substation after opening), or distributing master switch, branch switch, also can unfrequentl

19、y start the motor with large capacity. Application 1. Use ZK1 type vacuum circuit breaker united and divided master circuit, electrical valve, release, under-voltage release or manual controlled release, with the features of long-term life, less maintenance, security and so on. 2. With the protectio

20、ns of overload, short circuit, under-voltage and leakage, and with functions of electrical net insulation monitor, capacity current compensation, high-low voltage electric interlock, temperature alarming. Product features Model Instruction Moving substation using Rated voltage(V) Rated current(A) Va

21、cuum Mining flame-proof type Electricity-presenting switch K B Z / Y Main technical parameters Outline measure (mm) 950 570 950 660 1140 Rated voltage (V) Rated current (A) Utmost breaking ability (KA)(cos=0.35) 500 630 1140V 12.5 12.5 660V 15 15 Type, Specification KBZ- /1140(660)Y 3000 Electricity

22、 life (PCS) Cables outer dia. (,mm) 42 78 15000 Machinery life (PCS)KBZ-500 630(Z) Mining flame-proof vacuum feeding switch(intelligentized) The series electricity-presenting switches are used under coal mine which is full of explosive mixture gas such as methane, coal-dust and so on in medium surro

23、unded, in circuits of AC 50Hz, rated voltage 1140V or 660V, rated current to 630A, it can be as moving substation using electricity-presenting switch (connect coverboard with mov- ing substation after opening), or distributing master switch, branch switch, also can unfrequently start the motor with

24、large capacity. Application 1. Use ZK1 type vacuum circuit breaker united and divided master circuit, electrical valve, release, under-voltage release or manual controlled release, with the features of long-term life, less maintenance, security and so on. 2. With the protections of overload, short c

25、ircuit, under-voltage and leakage, and with functions of electrical net insulation monitor, capacity current compensation, high-low voltage electric interlock, temperature alarming. 3. LED display, clearance, intuination. Product features Model Instruction Intelligent Rated voltage(V) Rated current(

26、A) Vacuum Mining flame-proof type feeding switch K B Z / Z Main technical parameters 950 570 930 660 1140 Utmost breaking ability (KA)(cos=0.35) 500 630 1140V 12.5 12.5 660V 15 15 Rated voltage (V) Rated current (A) Type Specification 3000 Electricity life (PCS) 15000 Machinery life (PCS) Cables out

27、er dia. (,mm) 42 78 Outline measure (mm) WAROM 05 KBZ- /1140(660)ZSeries mining flame-proof vacuum feeding switch(intelligentized) KBZ-200 400Z Model Instruction Intelligent Rated voltage(V) Rated current(A) Vacuum Feeding switch Mining flame-proof type K B Z / Z Main technical parameters The series

28、 feeding switches are used under coal mine which is full of explosive mixture gas such as methane, coal-dust and so on in me- dium surrounded, in circuits of AC 50Hz, rated voltage 660V or 1140V , rated current to 400A, it can be as distributing master switch or branch switch, also can unfrequently

29、start the motor with large capacity. Application KBZ-200/1140(660)Z KBZ-400/1140(660)Z Utmost breaking ability (A)(cos=0.35) 7500 7500 Type Specificeotion WAROM 06 product features 1. The protecter adopts advanced MPU, with high intense datamanagement and advanced protect arithmatic, high protectpre

30、cision,and quick reaction. 2. Adopt apheliotropic LCD. Operate intuittonally and easily. 3. Can display system voltage,current and insulated values at realtime. 4. All kinds of protection function parameters can be selected andadjusted by menu, with wide application and high protectionprecision. 5.

31、With memory function, can memory failure type, failure time,failure current value and system voltage, etc bring conveniencefor check and maintenance. 6. With self-check function for soft and hard parts, For example,when the circuit goes wrong, the system will give messageaccordingly. 7. With functio

32、ns of selecting data communicating interface andchanging interface, connecting to control system, realizing remotecontrol and monitor, matching with RS-485 communicatinginterface according to users requirements. 8. With power supply which can only cut off failure point if selective leakege, thus red

33、uce the range of power-cut, and find failurepoint easily, reduce the time of power-cut, which is good for safeproduction. 3000 15000 Electricity life (PCS) Machinery life (PCS) 42 78 830 Outline measure (mm) Cables outer dia. (,mm) 660 1140 Rated voltage (V) Rated current (A) 200 400WAROM 07 The ser

34、ies feeding switches are used under coal mine which is full of explosive mixture gas such as methane, coal-dust and so on in me- dium surrounded, in circuits of AC 50Hz, rated voltage 660V or 1140V , rated current to 400A, it can be as distributing master switch or branch switch, also can unfrequent

35、ly start the motor with large capacity. Application 1. Use ZN7 type vacuum circuit breaker united and divided master circuit, manually controlled valve, release, under-voltage release or manually-controlled release, which has the features of long-term life, less maintenance, security and so on. 2. W

36、ith protections of overload, short-circuit, under voltage, leakage protection, leakage locking and so on. 3. Use intelligentized SCM treatment, display with digital tube, with memory function of failure current. Product features Main technical parameters Series mining flame-proof vacuum feeding swit

37、ch KBZ-200 400/1140(660)L Model Instruction Leakage protection Rated voltage(V) Rated current(A) Vacuum Feeding switch Mining flame-proof type K B Z / L Type Specificeotion 660 1140 KBZ-200/1140(660)L KBZ-400/1140(660)L Rated voltage (V) Rated current (A) Utmost breaking ability (A)(cos=0.35) 200 40

38、0 9000 7500 42 78 830 Outline measure (mm) Cables outer dia. (,mm) 3000 15000 Electricity life (PCS) Machinery life (PCS)WAROM 08 Series mining flame-proof vacuum feeding switch BKD9-200 400/1140(660)Z The series feeding switches are used under coal mine which is full of explosive mixture gas such a

39、s methane, coal-dust and so on in me- dium surrounded, in circuits of AC 50Hz, rated voltage 660V or 1140V , rated current to 400A, it can be as distributing master switch or branch switch, also can unfrequently start the motor with large capacity. Application Model Instruction BKD 9 / Z Vacuum Rate

40、d voltage(V) Rated current(A) Design no. Mining flame-proof feeding switch Explicating code 1. Use DW80-350 feeding switchs shell to make vacuum reform, with the features of long-term life, less maintenance,security and so on. 2. With protections of overload, short circuit, under voltage, leakage lo

41、cking, when type I out-connects checking-leakage relay, it has the protections of leakage, type II has the features of alternative leakage protection, short circuit test and leakage test. Product features Main technical parameters BKD9-200/1140(660)Z BKD9-400/1140(660)Z 3000 15000 Electricity life (

42、PCS) Machinery life (PCS) 650 510 860 Type Specification Utmost breaking ability (A)(cos=0.35) 7500 28 65 Cables outer dia. (,mm) Type I is ordinary Type II with alternativeleakage protection Outline measure (mm) 9000 Instanance current- release setting current (A) 200-1200 400-2400 1140 660 200 400

43、 Rated voltage (V) Rated current (A)WAROM 09 KBM-350(200)/660(380)( DW80) Model Instruction Rated voltage(V) Rated current(A) Others switch Flame-proof type Feeding K B M / Main technical parameters 380 660 KBM-200 KBM-350 Utmost distribution ability(KA) Cables outer dia. (,mm) 200 350 200-600 400-1

44、200 660V 7 7 Instanance current-release setting current(A) 380V 10 10 Controlled circuit 26 50 26 50 12-22 570 510 780 Type Specification Rated voltage (V) Rated current (A) Main circuit Series mining flame-proof vacuum feeding switch The series feeding switches are used under coal mine which is ful

45、l of explosive mixture gas such as methane, coal-dust and so on in me- dium surrounded, in circuits of AC 50Hz, rated voltage 660V or 380V , rated current to 350A, it can be as distributing master switch or branch switch, also can unfrequently start the motor with large capacity. Application 1. Simp

46、le structure and be convenient to maintain. 2. With features of instantance short-circuit protection andrelease. 3. When out-connecting checking-leakage relay, it has the pro-tection of leakage. Product features Outline measure (mm)WAROM 10 Series mining flame-proof vacuum electricity-presenting swi

47、tch (leakage selection) The series electricity-presenting switches are used under coal mine which is full of explosive mixture gas such as methane, coal-dust and so on in medium surrounded, in circuits with AC 50Hz, rated voltage 660V or 380V, rated current to 350A, it can be as distributing master

48、switch or branch switch, also can unfrequently start the motor with large capacity. Application 1. Simple structure and be convenient to maintenance. 2. With features of instantance short-circuit protection andrelease. 3. Can connect special checking-leakage relay externally andrealize functions of

49、leakage protection and leakage selected. Product features KBM-350(200)G( DW80) Main technical parameters Model Instruction Leakage selection Rated voltage(V)Rated current(A) Others switch Flame-proof type Feeding K B M / G 380 660 KBM-200 KBM-350 Utmost breaking ability(KA) Cables outer dia. (,mm) 200 350 200-600 400-1200 660V 7 7 Instanance current-release setting current (A) 380V 10 10 Controlled circuit 26 50 26 50 12-22 570 510 780 Type Specification Rated voltage (V) Rated current (A) Main circuit Outline measure (mm)WAROM 11 Model Instruction Intelligen

展开阅读全文